APR-B10
器件描述:AC Current transducer APR-B10
文件大小:56.74KB,共2页
Sponsor by e络盟
器件资料摘要:
Electrical data
Primary Nominal Current Analogue Output Signal Type
IPN (A.t.RMS) VOUT (V)
10,25,50 0-5V or 0-10V APR 50 B10
50,75,100 0-5V or 0-10V APR 100 B10
100,150,200 0-5V or 0-10V APR 200 B10
200,300,400 0-5V or 0-10V APR 400 B10
R L Load resistance ≥ 10 kΩ
VC Supply voltage +24 ±5% V DC
Vd R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn 5 kV
Limitation of voltage output 18 V
Accuracy-Dynamic performance data
X Accuracy @ IPN, TA = 25°C (without offset) < ±1 % of IPNe
L Linearity (0 .. ± IPN) < ±0.5 % of IPNV
OE Electrical offset voltage, TA = 25°C < ±0.5 % of IPNV
OT Thermal drift of VOE ±1 mV/KTCe
G Thermal drift of the gain (% of reading) ±0.1 %/K
t r Response time @ 90% of IP < 1000 ms
f Frequency bandwidth (-3 dB) 10 .. 6000 Hz
General data
TA Ambient operating temperature -20 .. +60 °C
TS Ambient storage temperature -20 .. +85 °C
m Mass 90 g
Protection type IP20
Reliable isolation according to EN50178, EN61010 300 V AC
Creepage distance > 5.5 mm
EMC in accordance with EN50082-2
Plastic according to UL94V0, CTI 1
Notes : Installation and maintenance should be done with power supply disconnected.
AC Current transducer APR-B10
Split core transducer for the electronic measurement distorted AC
waveforms current, with galvanic isolation between the primary (High
power) and the secondary circuits (Electronic circuit). Switch selectable
ranges and True RMS 0-5V and 0-10V switch selectable voltage output.
IPN = 10 .. 400 A
030708/0
Features
• VFD and SCR waveforms current
measurement
• True RMS output
• Split core type
• 5V & 10V switch selectable voltage
output.
• DIN mounting & Panel mounting
• Eliminates insertion loss
• Switch selectable ranges
Advantages
• Large aperture for cable up to Ø18mm
• High isolation between primary and
secondary circuits
• Easy to mount
Applications
• VFD Controlled Loads:
VFD output indicates how the motor
and attached load are operating.
• SCR Controlled Loads:
Acurate measurement of phase angle
fired or burst fired (time proportioned)
SCRs. Current measurement gives
faster response than temperature
measurement.
• Switching Power Supplies and
Electronic Ballasts:
True RMS sensing is the most
accurate way to measure power
supply or ballast input power.
LEM Components www.lem.com
Preliminary