AP-B420L
器件描述:AC Current transducer AP-B420L
文件大小:56.95KB,共2页
Sponsor by e络盟
器件资料摘要:
Electrical data
Primary Nominal Current Analogue Output Signal Type
IPN (A.t.RMS) IOUT (mA)
10,25,50 4-20 AP 50 B420L
50,75,100 4-20 AP 100 B420L
100,150,200 4-20 AP 200 B420L
200,300,400 4-20 AP 400 B420L
R L Load resistance < 350 Ω
VC Supply voltage (loop powered) +24 V DC
Vd R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn 5 kV
Limitation of output current < 25 mA
Accuracy-Dynamic performance data
X Accuracy @ IPN, TA = 25°C (without offset) < ±1 % of IPNe
L Linearity (0 .. ± IPN) < ±0.5 % of IPNI
OE Electrical offset current, TA = 25°C 4 mAI
OT Thermal drift of IOE ±1 µA/KTCe
G Thermal drift of the gain (% of reading) ±0.1 %/K
t r Response time @ 90% of IP < 500 ms
f Frequency bandwidth (-3 dB) 10 .. 6000 Hz
General data
TA Ambient operating temperature -20 .. +60 °C
TS Ambient storage temperature -20 .. +85 °C
m Mass 90 g
Protection type IP20
Reliable isolation according to EN50178, EN61010 300 V AC
Creepage distance > 5.5 mm
EMC in accordance with EN50082-2
Plastic according to UL94V0, CTI 1
Notes : Installation and maintenance should be done with power supply disconnected.
AC Current transducer AP-B420L
Split core transducer for the electronic measurement AC waveforms
current, with galvanic isolation between the primary (High power) and
the secondary circuits (Electronic circuit). Switch selectable ranges
and RMS 4-20mA current output.
IPN = 10 .. 400 A
030708/0
Features
• RMS output
• Split core type
• Loop powered 4-20mA current output
• DIN mounting & Panel mounting
• Eliminates insertion loss
• Switch selectable ranges
Advantages
• Large aperture for cable up to Ø18mm
• High isolation between primary and
secondary circuits
• Easy to mount
Applications
• Automation systems
Analog current reading for remote
monitoring (e.g. motor) and software
alarms.
• Panelmeters
Simple connection displays power
consumption.
LEM Components www.lem.com
Preliminary