AP-B10
器件描述:AC Current transducer AP-B10
文件大小:56.39KB,共2页
Sponsor by e络盟
器件资料摘要:
Electrical data
Primary Nominal Current Analogue Output Signal Type
IPN (A.t.RMS) VOUT (V)
10,25,50 0-5V or 0-10V AP 50 B10
50,75,100 0-5V or 0-10V AP 100 B10
100,150,200 0-5V or 0-10V AP 200 B10
200,300,400 0-5V or 0-10V AP 400 B10
R L Load resistance ≥ 10 kΩ
VC Supply voltage +24 ±5% V DC
Vd R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn 5 kV
Limitation voltage output 18 V
Accuracy-Dynamic performance data
X Accuracy @ IPN, TA = 25°C (without offset) < ±1 % of IPNe
L Linearity (0 .. ± IPN) < ±0.5 % of IPNV
OE Electrical offset voltage, TA = 25°C < ±0.5 % of IPNV
OT Thermal drift of VOE ±1 mV/KTCe
G Thermal drift of the gain (% of reading) ±0.1 %/K
t r Response time @ 90% of IP < 500 ms
f Frequency bandwidth (-3 dB) 10 .. 6000 Hz
General data
TA Ambient operating temperature -20 .. +60 °C
TS Ambient storage temperature -20 .. +85 °C
m Mass 90 g
Protection type IP20
Reliable isolation according to EN50178, EN61010 300 V AC
Creepage distance > 5.5 mm
EMC in accordance with EN50082-2
Plastic according to UL94V0, CTI 1
Notes : Installation and maintenance should be done with power supply disconnected.
AC Current transducer AP-B10
Split core transducer for the electronic measurement AC waveforms
current, with galvanic isolation between the primary (High power) and
the secondary circuits (Electronic circuit). Switch selectable ranges
and RMS 0-5V and 0-10V switch selectable voltage output.
IPN = 10 .. 400 A
030708/0
Features
• RMS output
• Split core type
• 5V & 10V switch selectable voltage
output.
• DIN mounting & Panel mounting
• Eliminates insertion loss
• Switch selectable ranges
Advantages
• Large aperture for cable up to Ø18mm
• High isolation between primary and
secondary circuits
• Easy to mount
Applications
• Automation systems
Analog current reading for remote
monitoring (e.g. motor) and software
alarms.
• Panelmeters
Simple connection displays power
consumption.
LEM Components www.lem.com
Preliminary