2CC125-200
器件描述:British Dimension HRCII-C Fuses
文件大小:416.04KB,共1页
Sponsor by e络盟
器件资料摘要:
163
British Dimension HRCII-C Fuses
600 Volts AC
a73
2 – 600 Amperes
HRCII-C fuses are stud-mounted fuses designed to British
standard dimensions. They are generally used for motor short
circuit protection in dead-front holders, and are normally
required to be used in conjunction with a motor running
overload device.
SPECIFICATIONS
Voltage Rating: 600 Volts AC, 250 Volts DC
Interrupting Rating: 200,000 amperes rms symmetrical AC
80,000 amperes rms symmetrical DC
Ampere Range: 2 – 600 amperes
Approvals: CSA Certified to Standard C22.2 No. 106-M90
(File No. LR90341)
AMPERE RATINGS
2CO 2 10255080
4 530601
62040
2CC 125 200 300 400 500
150 250 350 450 600
2CM 80 125 200 300 400
100 150 250 350
Example part number (series & amperage): 2CM 150
RECOMMENDED FUSE BLOCKS
DF30 (F, B, FB) — Fits 2 – 30 amps
DF60 (F, B, FB) — Fits 40 – 60 amps
DF100 (F, B, FB)— Fits 80 – 100 amps
For additional information on HRCII-C fuse holders,
contact factory.
CAT. NO.
DIMENSIONS IN MM (Inches in parentheses)
1
56 21 — 85 9 1 73 5.5 7.5 —
(2.2) (0.83) (3.3) (0.35) (0.04) (2.87) (0.21) (0.29)
1
57 26 — 88 13 1.6 73 5.5 7.5 —
(2.24) (1.02) (3.45) (0.51) (0.06) (2.87) (0.21) (0.29)
1
68 36 — 110 19 2.4 94 8.7 — —
(2.88) (1.42) (4.33) (0.75) (0.09) (3.7) (0.34)
2
76 41 — 137 19 3.6 111 8.7 16 —
(3) (1.61) (5.39) (0.75) (0.14) (4.37) (0.34) (0.63)
3
81 58 — 210 26 6.5 133 10.3 16 25.4
(3.19) (2.28) (8.27) (1.02) (0.26) (5.24) (0.4) (0.63) (1)
3
83 74 — 210 26 6.5 133 10.3 16 25.4
(3.27) (2.91) (8.27) (1.02) (0.25) (5.24) (0.4) (0.63) (1)
2
66 31 — 135 19 3.6 111 8.7 16 —
(2.6) (1.22) (5.31) (0.75) (0.14) (4.37) (0.34) (0.63
1
77 41 — 110 19 2.4 94 8.7 10.3 —
(3.03) (1.81) (4.33) (0.75) (0.09) (3.7) (0.34) (0.4)
2
81 58 — 136 26 5.2 111 8.7 16 —
(3.19) (2.25) (5.35) (1.02) (0.2) (4.37) (0.34) (0.63)
OLD LF
PART NO.
REFER TO
FIG. NO.
FII
FII
FII
FIIC
FIIC
FIIC
FIIM
FIIM
FIIM
*Hole diameter to accept insulated stud (types C and D) mm min
2CO 2-30
2CO 40-60
2CO 80-100
2CC 125-200
2CC 250-400
2CC 450-600
2CM 80-100
2CM 125-200
2CM 250-400
J J
F
B
B
A
G
D
F
H
H
A
G
G
D
K
E
E
FIG. 1 FIG. 2
FIG. 3
ABCDEFGHJK