EEWorld首页 新闻 论坛 博客 白皮书 专题 电子电路 电子器件 单片机 嵌入式 模拟电路 DSP FPGA 电源管理 手机/便携 医疗电子 汽车电子 工业控制
厂商索引:A-B-C-D-E-F-G-H-I-J-K-L-M-N-O-P-Q-R-S-T-U-V-W-X-Y-Z

587B062

器件描述:240V AC POWER LINE SURGE SUPPRESSOR
器件厂商:PROTEC [Protek Devices]
文件大小:97.45KB,共3页
Sponsor by e络盟
器件资料摘要:
587B062
thru
587B302
105047.R4 12/03 www.protekdevices.com
240V AC POWER LINE SURGE SUPPRESSOR
Only One Name Means ProTek’Tion™
05047
APPLICATIONS
✔ Hard Wired Equipment AC Power Protection
✔ Load Side Distribution Systems
✔ Secondary Protection for Light Industrial AC Power
IEC COMPATIBILITY (EN61000-4)
✔ 61000-4-5 (Surge): 1kA, 8/20µs - Level 4(Line-Line)
FEATURES
✔ Meets ANSI/IEEE C62.41 Requirements
✔ Listed to CSA, File LR65240
✔ Differential Mode Protection
✔ Low Clamping Voltage
✔ Nanosecond Response Time
✔ Long Life and Maintenance Free
MECHANICAL CHARACTERISTICS
✔ Plastic Package
✔ Weight: 485 Grams (Approximate)
✔ Flammability Rating UL 94V-0
✔ Device Marking: Part Number, Date Code, Logo, Voltage and Current Rating
DESCRIPTION
The 587B Series of 240 Volt AC Surge Suppressors is designed for use by the OEM,
equipment installer and or maintenance contractor. These modules employ a three
stage technology proven to be the most cost effective and reliable method in protect-
ing sensitive electronic equipment from over voltage transients.
This series is designed to protect AC powered equipment from the 6,000 volt peak
open circuit voltage and 3,000 Amp short circuit current as defined in ANSI/IEEE
C62.41, Category C1.
The 587B Series offers a high degree of protection against 240 VAC EMI line noise. It
is ideal for protecting 800 Volt components because the solid state TVS technology
assures that the line-to-neutral voltage will not exceed 800 Volts. While the modules
are designed for transient voltage protection, the advanced circuitry will also attenuate
the amplitude and slow the rate of rise of high frequency noise acting as an EMI filter.
The 587B Series includes differential mode protection, which is effective in reducing
interference from line to equipment and are effective in reducing equipment gener-
ated noise to meet FCC, VDE and CSA interference requirements.
U.S PATENT 4,563,720
0 10 20 30 40 50 60
0 10 20 30 40 50 60
FIGURE 2
TYPICAL CLAMPING ACTION
OF A 16 AMP MODULE
Kilovolts
Time - µs
0
2
6
4
FIGURE 1
TRANSIENT VOLTAGE THREAT
CONDITION
Kilovolts
Time - µs
0
2
4
8
6
Figures 1 and 2 are photographs of digitized waveforms
showing the typical clamping action of a 16 ampere module.
A 12 Ohm resistor is used to represent a 10 Amp equipment
load. The load is then subjected to the ANSI/IEEE C62.41
Category CI test conditions (6,000V/3,000A). These photo-
graphs contrast the effect on equipment with and without the
protector.